Power Logger
Technical Specifications
53
Operating error: ±(0.5 % of m. v. + 10 digit)
Resolution: 0.1 V
V-RMS Delta measurement
Measuring range: 100 / 115 / 190 /208 / 220 / 380 / 400 / 415
/ 450 / 480 / 600 / 660 / 690 / 720 / 830 V
AC
Intrinsic error: ±(0.2 % of m. v. + 5 digit)
Operating error: ±(0.5 % of m. v. + 10 digit)
Resolution: 0.1 V
A-RMS measurement
Fluke Flexi sets and current probes with voltage output are supported. All
current probes must correspond to 600 V / CAT III
Flexi set I
N
ranges: 15 / 150 / 3000 A RMS (at sine)
Current clamp ranges: 5 / 50 / 500 mV AC
Resolution: 0.01 A
Ranges:
150 / 3000 A 50 mv / 500 mV output
Intrinsic error: ±(0.5% of m. v. + 10 digit)
Operating error: ±(1% of m. v.+ 10 digit)
15 A 5 mV output
Intrinsic error: ±(0.5% of m. v. + 20 digit)
Operating error: ±(1% of m. v. + 20 digit)
The errors of the current probes are not considered.
By using Fluke flexi-set:
Flexi set measuring error: ±(2 % of m. v. + 10 digit)
Position influence: ±(3 % of m. v. + 10 digit)
CF (typical): 2.83