Install Pressure Sensor
The discharge pressure sensor is mounted on the discharge manifold of the pump.
If there is a check valve in the discharge side of the pump, mount the discharge sensor
before the check valve. T-fittings can be used to mount the pressure sensors.
Note: Install the pressure sensor upright so that the water in the end of the
sensor is able to drain back into the pipe.
1. Screw the sensor into a 1/4-18 NPT hole.
Caution: Do not use the main body that houses the electronics to tighten the
pressure sensor. Damage to the sensor may occur.
2. Tighten the sensor with a 3/4-inch wrench on the lower hex fitting.
3. Connect the pressure sensor cable from the control module to the pressure
sensor. (Refer to Wiring section.)
Figure 3. Pressure Sensor Dimensions
Caution: Do not use the main
body that houses the electronics
to tighten the sensor. Damage to
the sensor may occur.
















