PBA100 Rev0407
20
Preset Settings (Pressure or RPM)
The preset button allows the operator to go to a pre-programmed pressure or
RPM setting during operations. The setting will be shown in the message display. This
procedure is to change the setting in the program.
Note: The engine must be running and the pump engaged interlock circuit
must be closed (the THROTTLE READY LED must be on).
1. Press IDLE button.
Result: Engine goes to idle RPM
2. Press PSI or RPM mode button to select the setting to be changed.
Result: LED indicator goes on for mode selected.
Note: The RPM display must show IdLE before changing the preset.
3. Press and hold PRESET button. (Continue to hold through step 4.)
Result: Message display flashes then shows PSEt.
4. Rotate control knob to change preset setting.
5. Release PRESET button.
Result: The new preset is programmed. RPM display shows IdLE.
High Idle
The PumpBoss programming includes a high idle function.
To activate the high idle set interlocks as called for by SOP (normally this would
include the transmission in neutral and the parking brake on ). Set the High Idle switch
to ON.
Note: The pump must NOT be engaged when using the high idle function
and the THROTTLE READY LED will be off.
Change High Idle Setting
Note: The high idle is set at about 1000 RPM at the factory. (This value will
vary depending on the specific engine.)
1. With the engine running, set the high idle switch to ON.
2. Press and hold PRESET button for 3 seconds.
Result: RPM display will flash and show the high idle setting.
3. Keep pressing the PRESET button and rotate control knob to desired RPM.
4. Release PRESET button to store the new high idle setting.