PBA100 Rev0407
38
Figure 17. High Idle Wiring
A High Idle Kit is available from FRC.
P/N XE-TG38HK
Includes:
ON/OFF Switch
Indicator Light
Two Diodes
To 8-Pin Connector
Pin 6 White Wire
Interlock Input
To 12-Pin Connector
Pin 7 Violet Wire
High Idle Active Input
High Idle
ON/OFF
Switch
Diodes
(IN4002 or equivalent)
From
Transmission
Neutral
+ VDC
Pump
Engaged
Indicator
Light
NC
NO
C
ON
OFF
High Idle
Indicator
Light
GND
From
Pump
Engaged
+12 VDC
GND
NC
NO
C
From
Parking
Brake
GND
NC
NO
C
High Idle Wiring
The PumpBoss programming includes a high idle function. To activate the high
idle provide + VDC to pin 7 (High Idle Active Input) of the 12-pin connector and pin
6 (Interlock Input) of the 8-pin connector. The high idle connection to pin 6 must be
isolated form the interlock circuit using two diodes (see schematic).
Note: It is important that the connection to the Interlock Input from the High
Idle circuit be isolated from the apparatus interlock wiring with the two
diodes. Refer to the wiring diagram. The pump must NOT be engaged
when using the high idle function.
The high idle is set at about 1000 RPM at the factory. (This value will vary
depending on the specific engine.) To adjust this setting refer to High Idle in the
Operation Section.