26 PB
SPECIFICATIONS
Capacities and Selection Data frequency
5.CAPACITIES AND SELECTION DATA
Airflow
(CMF)
Outdoor
DB(°F)
IWB (°F) 59 63 67 71
IDB (°F) 70 75 80 85 70 75 80 85 70 75 80 85 70 75 80 85
750
5
TC
16.0 16.1 16.5 16.7 16.5 16.7 16.9 17.0 17.7 17.8 17.9 18.0 \ 21.1 21.3 21.6
S/T
0.99 1.00 1.00 1.00 0.61 0.83 1.00 1.00 0.39 0.57 0.73 0.90 \ 0.39 0.53 0.67
kW
0.98 0.99 1.00 1.00 1.00 1.02 1.03 1.03 1.03 1.04 1.06 1.07 \ 1.25 1.26 1.19
30
TC
16.7 16.9 17.2 17.4 17.2 17.4 17.6 17.8 18.4 18.6 18.7 18.8 \ 22.1 22.2 22.6
S/T
0.99 1.00 1.00 1.00 0.61 0.83 1.00 1.00 0.39 0.57 0.73 0.90 \ 0.39 0.53 0.67
kW
1.09 1.10 1.11 1.11 1.11 1.13 1.14 1.15 1.15 1.16 1.18 1.19 \ 1.39 1.40 1.33
65
TC
17.5 17.7 18.1 18.3 18.1 18.3 18.5 18.7 19.4 19.6 19.7 19.8 \ 23.2 23.4 23.7
S/T
0.99 1.00 1.00 1.00 0.64 0.88 1.00 1.00 0.39 0.59 0.78 0.99 \ 0.38 0.55 0.71
kW
1.21 1.23 1.24 1.24 1.24 1.25 1.27 1.28 1.28 1.29 1.31 1.32 \ 1.54 1.55 1.47
75
TC
17.6 17.8 18.2 18.4 18.2 18.4 18.6 18.8 19.5 19.6 19.8 19.9 \ 23.8 23.9 23.9
S/T
0.99 1.00 1.00 1.00 0.63 0.88 1.00 1.00 0.39 0.59 0.78 1.00 \ 0.38 0.55 0.71
kW
1.25 1.26 1.28 1.28 1.28 1.29 1.30 1.32 1.32 1.33 1.34 1.36 \ 1.70 1.70 1.70
85
TC
17.2 17.4 17.8 18.0 17.8 18.0 18.2 18.4 19.1 19.2 19.4 19.5 \ 22.4 22.5 22.7
S/T
0.99 1.00 1.00 1.00 0.64 0.89 1.00 1.00 0.39 0.59 0.79 1.00 \ 0.39 0.56 0.73
kW
1.41 1.42 1.44 1.44 1.44 1.46 1.47 1.48 1.49 1.50 1.51 1.53 \ 1.81 1.83 1.84
95
TC
16.8 17.0 17.3 17.5 17.3 17.5 17.7 17.9 18.6 18.7 18.8 19.0 \ 21.3 21.4 21.4
S/T
1.00 1.00 1.00 1.00 0.64 0.90 1.00 1.00 0.39 0.60 0.80 1.00 \ 0.39 0.57 0.75
kW
1.66 1.67 1.69 1.69 1.69 1.71 1.73 1.74 1.76 1.77 1.78 1.79 \ 2.05 2.05 2.05
105
TC
16.3 16.5 16.9 17.1 16.9 17.1 17.2 17.4 18.1 18.2 18.3 18.5 \ 19.5 19.6 19.5
S/T
1.00 1.00 1.00 1.00 0.65 0.90 1.00 1.00 0.39 0.60 0.81 1.00 \ 0.39 0.59 0.79
kW
1.93 1.95 1.97 1.97 1.97 2.00 2.01 2.04 2.05 2.07 2.08 2.09 \ 2.15 2.16 2.13
115
TC
13.0 13.1 13.5 13.6 13.5 13.6 13.8 13.9 14.5 14.6 14.6 14.7 \ 15.5 15.6 15.7
S/T
1.00 1.00 1.00 1.00 0.66 1.00 1.00 1.00 0.40 0.66 0.93 1.00 \ 0.40 0.65 0.90
kW
1.71 1.73 1.75 1.75 1.75 1.77 1.78 1.80 1.82 1.83 1.84 1.85 \ 1.91 1.91 1.92
122
TC
11.1 11.2 11.4 11.6 11.4 11.6 11.7 11.8 12.3 12.4 12.4 12.5 \ 13.2 13.3 13.3
S/T
1.00 1.00 1.00 1.00 0.62 0.85 1.00 1.00 0.40 0.60 0.79 0.99 \ 0.39 0.58 0.76
kW
1.76 1.78 1.80 1.80 1.80 1.82 1.84 1.86 1.88 1.89 1.90 1.90 \ 1.96 1.97 1.97
Performance data (Heating operation at rated frequency)
24K outdoor unit matches 18K indoor unit
Airflow
(CFM)
ID OD
75 65 55 47 35 25 15 5 -4 -13
450
60
TC 21.2 21.2 21.2 20.3 17.3 16.1 13.5 12.5 10.9 8.2
kW 1.22 1.31 1.53 1.67 1.55 1.66 1.50 1.48 1.41 1.13
70
TC 16.4 16.3 16.3 16.1 16.1 15.8 13.2 12.3 10.7 8.0
kW 0.91 0.96 1.13 1.32 1.59 1.80 1.64 1.60 1.51 1.21
75
TC 13.8 13.8 13.8 13.8 13.6 13.6 12.5 11.5 9.8 7.4
kW 0.76 0.82 0.95 1.13 1.31 1.53 1.71 1.66 1.57 1.26
80
TC 11.3 11.3 11.3 11.3 11.2 11.1 11.1 11.1 9.6 7.2
kW 0.63 0.67 0.79 0.92 1.09 1.23 1.55 1.69 1.64 1.31
600
60
TC 23.7 23.7 23.0 20.6 17.5 16.3 13.8 12.8 11.1 8.3
kW 1.45 1.53 1.70 1.64 1.53 1.65 1.52 1.48 1.42 1.14
70
TC 18.4 18.3 18.1 18.0 17.1 16.0 13.4 12.5 10.9 8.2
kW 1.05 1.13 1.29 1.49 1.67 1.78 1.64 1.60 1.52 1.22
75
TC 15.5 15.4 15.4 15.2 15.2 15.2 12.7 11.7 9.9 7.4
kW 0.89 0.94 1.10 1.25 1.50 1.76 1.71 1.66 1.57 1.26
80
TC 12.7 12.7 12.7 12.6 12.5 12.4 12.5 11.5 9.8 7.4
kW 0.73 0.77 0.90 1.04 1.22 1.41 1.77 1.73 1.64 1.31
750
60
TC 26.4 26.0 23.4 20.9 17.8 16.6 14.0 13.0 11.3 8.5
kW 1.70 1.74 1.69 1.64 1.55 1.66 1.55 1.51 1.45 1.16
70
TC 20.3 20.2 20.2 20.2 17.4 16.2 13.7 12.7 11.1 8.3
kW 1.21 1.29 1.51 1.76 1.68 1.79 1.66 1.62 1.55 1.24
75
TC 17.3 17.2 17.0 17.0 17.0 16.0 12.9 11.9 10.2 7.7
kW 1.03 1.09 1.24 1.46 1.73 1.87 1.73 1.69 1.61 1.29
80
TC 14.2 14.2 14.2 14.1 13.9 13.9 12.8 11.7 10.0 7.5
kW 0.86 0.91 1.04 1.22 1.41 1.63 1.80 1.75 1.66 1.33
(°F)
(°F)