12– Temperature Setback Delay - Heat
00-120 (20* default setting)
Select the time delay (in minutes) for which the room that is in the guest
occupancy mode needs to be unoccupied before the temperature setback is
initiated.
This feature prevents initiating temperature setback prematurely while the guest
is still in the room but in an area where occupancy cannot be detected by the
occupancy sensor.
Setting the “Temperature Setback Delay - Heat” to “00”, disables the setback in
the heat mode. Set to “00” to disable EMS.
Custom Energy Savings Settings