Wall Controller is not controlling the VRP
®
unit.
Verify the status of the red light on the Wireless Receiver;
The red light is off
The Wireless Receiver is not powered. Verify that the Wireless Receiver is
properly wired to the VRP unit - specically make sure that the V+ and V-
wires are properly connected;
If the red light is blinking with one (1) ash
The Wireless Receiver is powered but it is not communicating with the
Wall Controller, turn the Wall Controller off and on to re-initiate the linking
procedure.
In case of a Network Installation, re-link the Wall Controller and the
Wireless Controll Card with the Network Programmer.
The red light is blinking with three (3) ashes.
The Wireless Receiver is communicating with the Wall Controller. Verify
that the Wireless Receiver is properly wired to the VRP unit - specically
make sure that the D+ and the D- wires are properly connected.