EasyManua.ls Logo

Friedrich VRPXEMWRT2 - Temperature Setback Delay - Cool

Friedrich VRPXEMWRT2
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
14 – Temperature Setback Delay- Cool
00-120 (20* default setting)
Select the time delay (in minutes) for which the room that is in the guest
occupancy mode needs to be unoccupied before the temperature setback is
initiated.
This feature prevents initiating temperature setback prematurely while the guest
is still in the room but in an area where occupancy cannot be detected by the
occupancy sensor.
Setting the “Temperature Setback Delay - Cool” to “00”, disables the setback in
the cool mode. Set to “00” to disable EMS.
Custom Energy Savings Settings
VPXEMWRT2-Thermostat Manual_pkg.indd 35 2017-12-15 3:37 PM