43
22 – Automatic Humidity Control
†
00 Disable automatic humidity control;
01 * Enable automatic humidity control;
When “Automatic Humidity Control” is enabled
, Wall Controller will turn on air
conditioning in an unoccupied room when humidity raises above 60% and room
temperature is above 72°F until either room humidity is below 55% or room
temperature is below 72°F
;
* Indicates default setting;
†
This setting is active only on Wall Controllers with enabled humidity features.
Changing this setting on a non-humidity Wall Controller will have no effect on
Wall Controller operation.
Humidity features can be enabled on compatible Wall Controllers via remote
management.
Certain models only. Additional fees apply.
Custom Energy Savings Settings
VPXEMWRT2-Thermostat Manual_pkg.indd 43 2017-12-15 3:37 PM