59
Solar Module
Ground at
Positive Pole:
Connecting
Solar Module
Strings with a
Cable Cross
Section > 16
mm²
(continued)
Important! When using connection distributors (copper plate), insert 6
metal bolts with fuse covers in the fuse holder.
The metal bolts are included in the Fronius IG Plus scope of delivery.
14
1
3
2
15
2
1
Important
- Set the jumper from the ‘SMON position to the ‘SMOFF position for
correct measurement results
- Check the polarity and voltage of the DC cable: the voltage should
be a max. of 600 V.
13
max. 600 V