Protection devices
AFPE (AFCI) classification (according
to IEC63027)
11)
= F-I-AFPE-1-4-1
Full coverage
Integrated
AFPE
1 monitored string per input port
4 input ports per channel (MPP1: 2,
MPP2: 2)
1 monitored channel
Data communication
WLAN SMA-RP connection
(FCC ID: QKWPILOT01 / IC ID:
12270A-PILOT01)
802.11b/g/n (WPA, WPA2)
Frequency: 2.4 GHz
Ethernet (LAN) RJ45, 10/100 MBit
Wired shutdown (WSD) Max. 28 devices / WSD chain
Max. distance between two devices =
100 m
Modbus RTU SunSpec (2x) RS485 2-wire
Voltage level of digital inputs Low: min. 0 V – max. 1.8 V
High: min. 4.5 V – max. 28.8 V
Input currents of digital inputs Depending on the input voltage;
input resistance = 70 kOhm
Total power for digital output
(internal supply)
6 W at 12 V (USB not connected)
Power per digital output
(external supply)
1 A at >12.5 V – 24 V
(max. 3 A in total)
Datalogger/web server Integrated
Fronius Primo
GEN24 3.6 / 3.6
Plus
DC input data
MPP voltage range
(at rated power)
200 – 530 V
Max. input voltage
at 1000 W/m² / -10°C in an open cir-
cuit
600 V
Min. input voltage 65 V
Feed-in start-up input voltage in grid
operation
5)
80 V
Max. input current
PV 1
PV 2
22.0 A
12.0 A
Max. short circuit current of module
array (I
SC PV
)
PV 1
PV 2
36 A
19 A
185