IMPORTANT!
The inverter can be fused with max. an
automatic circuit breaker 63 A.
Inverter
Phase
s
AC out-
put
Maximum
fuse rating
Recom-
mended
fuse rating
Fronius Primo GEN24 3.0 kW 1 3 000 W 63 A 32 A
Fronius Primo GEN24 3.6 kW 1 3 680 W 63 A 32 A
Fronius Primo GEN24 4.0
kW
1 4 000 W 63 A 40 A
Fronius Primo GEN24 4.6 kW 1 4 600 W 63 A 40 A
Fronius Primo GEN24 5.0
kW
1 5 000 W 63 A 40 A
Fronius Primo GEN24 6.0
kW
1 6 000 W 63 A 40 A