2-9 
 
No output circuit filter inserted  Output circuit filter inserted 
 
 
 
•  Do not connect a power factor correcting capacitor or surge absorber to the inverter’s 
output lines (secondary circuit). 
•  If the wiring length is long, the stray capacitance between the wires will increase, 
resulting in an outflow of the leakage current. It will activate the overcurrent protection, 
increase the leakage current, or will not assure the accuracy of the current display. In 
the worst case, the inverter could be damaged. 
•  If more than one motor is to be connected to a single inverter, the wiring length should 
be the length of the wires to the motors. 
 
 
 Driving 400 V series motor 
•  If a thermal relay is installed in the path between the inverter and the motor to protect 
the motor from overheating, the thermal relay may malfunction even with a wiring 
length shorter than 50 m. In this situation, add an output circuit filter (option) or lower 
the carrier frequency (Function code F26: Motor sound (Sound tune)). 
•  If the motor is driven by a PWM-type inverter, surge voltage that is generated by 
switching the inverter component may be superimposed on the output voltage and 
may be applied to the motor terminals. Particularly if the wiring length is long, the surge 
voltage may deteriorate the insulation resistance of the motor. Consider any of the 
following measures. 
-  Use a motor with insulation that withstands the surge voltage. (All Fuji standard 
motors feature insulation that withstands the surge voltage.) 
-  Connect an output circuit filter (option) to the output terminals (secondary circuits) of 
the inverter. 
-  Minimize the wiring length between the inverter and motor (10 to 20 m or less). 
 
 
 Wiring length for EMC filter built-in type 
•  When the wiring length between the inverter and motor exceeds 10 m, the filter circuit 
may be overheated and damaged due to increase of leakage current. To reduce the 
leakage current, set the motor sound (carrier frequency) to 2 kHz or below with func-
tion code F26. 
 
 
Motor 
50 m or less
Output circuit filter 
400 m or less 
5 m or less
Motor 
Power 
supply
Inverter 
Power 
supply
Inverter