Chapter 2 Description of Functions
83
Analog channel signal selection items (trace back)
No Item
Fast
/Lower
Note
0
Speed setting 2 (before calculating
acceleration/deceleration)
Lower
1 Speed setting 4 (ASR input) Lower
2 Speed detected value Lower
3 Torque command Lower
100%:Rated motor torque
4
Torque current command
Lower
100%:Rated motor torque (P09,A11,A111)
5
Torque current calculation value
Lower
100%:Motor rated torque current
(P09,A11,A111)
6 Exciting current command Lower
100%:Motor rated excitation current
(P08,A10,A110)
7 Exciting current detection Lower
100%:Motor rated excitation current
(P08,A10,A110)
8 Magnetic-flux calculation Lower
9
Output current effective value
Lower
10
Output voltage effective value
Lower
11
DC intermediate voltage
Lower
12
Motor temperature
Lower
13 Line speed detected value Lower
14 U phase voltage detected value Lower
100%: Motor rated voltage (F05,A04,A104)
15 V phase voltage detected value Lower
100%: Motor rated voltage (F05,A04,A104)
16 W phase voltage detected value Lower
100%: Motor rated voltage (F05,A04,A104)
17 Cooling fin temperature Lower
18 PID output Lower
19 Torque bias Lower
20 Ai1 adjusted value Lower
10000/10V
21 Ai2 adjusted value Lower
10000/10V
22 U phase current detected value Fast
100%: Motor rated current (P04,A03,A103)
23 V phase current detected value Fast
100%: Motor rated current (P04,A03,A103)
24 W phase current detected value Fast
100%: Motor rated current (P04,A03,A103)
25 Electric angle Fast
8192/360°
26 Reserve 1 (No polarity) Fast
* Do not set.
27 Reserve 1 (With polarity) Fast
* Do not set.
28 Reserve 2 (No polarity) Fast
* Do not set.
29 Reserve 2 (With polarity) Fast
* Do not set.
30 Reserve 3 (No polarity) Lower
* Do not set.
31 Reserve 3 (With polarity) Lower
* Do not set.
32 Reserve 4 (No polarity) Lower
* Do not set.
33 Reserve 4 (With polarity) Lower
* Do not set.
If you choose a mixture of high-speed data and low-speed data, displays only part
of the low-speed data that was retrieved for the time axis to the length of the
high-speed data side.