Appendix 2 Automatic Update of System Software
<Measures when an abnormality occurs>
If an abnormality occurs during update by the system software utility because “the SPF is powered off” or “the loader cable is
disconnected,” the following dialog box appears.
Perform update again following the procedure below.
(1) Click the [Forced ending] button to close the system software utility.
(2) Power off the SPF once.
(3) Check the connection of the loader cable.
(4) Power on the SPF again.
(5) Open the explorer and start up the system software utility “SPFUtl.exe”.
The folder where “SPFUtl.exe” is stored depends on the loader and installation destination.
Example of SX-Programmer Expert (D300win)
C:\D300win\Spbutl\SPFUtl.exe
Example of SX-Programmer StandardV3
C:\Program Files\Fuji Electric\SX-Programmer Standard\Spbutl\SPFUtl.exe
(6) Following the <Update procedure>, perform update again.