Handling of TS Series Components
DIPSW1
*
(Storage automatic upload)
Set the DIPSW1 to ON when automatically uploading screen data from storage such as a USB
memory.
Procedure
1. Preparation of storage
Prepare storage such as a USB memory with screen data written from V-SFT-5. (For the loading
procedure, refer to the V8 Series Reference Manual.)
2. Connection of storage
Turn off the TS unit. Connect the storage device to the USB-A port.
3. DIP switch setting
Slide the DIPSW1 to ON.
4. Automatic upload start
Turn on the TS unit. Screen data is automatically loaded into the flash memory of the TS unit.
* Be sure to set the DIPSW1 to OFF when automatic upload is not performed.
DIPSW2 and DIPSW3 (COM1 switching between 4-wire and 2-wire)
When connecting a controller to COM1 via RS-422/485 (2-wire connection), set the DIPSW2 and
DIPSW3 to ON.
When connecting a controller to COM1 via RS-422/485 (4-wire connection), set the DIPSW2 and
DIPSW3 to OFF.
DIPSW4 and DIPSW5 (PPI/MPI terminating resistance setting)
When connecting a Siemens PLC (PPI/MPI) to COM1, set the DIPSW4 and DIPSW5 to ON.
DIPSW6, DIPSW7, and DIPSW8 (terminating resistance setting)
When connecting a controller to COM1 via RS-422/485 (2-wire connection), set the DIPSW7 to
ON.
When connecting a controller to COM1 via RS-422/485 (4-wire connection), set the DIPSW6 and
DIPSW7 to ON.
When connecting a controller to COM3 via RS-422/485 (2-wire connection), set the DIPSW8 to
ON.