5-10 2. Main Menu Screen
Setting using the V-SFT Editor
1. Select [System Setting] [Ethernet Communication] [Local Port IP Address] on the V-SFT
editor. The [IP Address Setting] dialog is displayed.
2. Check the [Set IP] check box and set each item.
* For more information on setting items, refer to page 5-11.
3. Click [OK].
4. Transfer the screen data to the TS unit. Check the IP address displayed under [Ethernet
Information] on the Main Menu screen.
Select IP Address from
Network Table
This is valid when the IP address of the TS has been registered in the
network table. Select a network table number from 0 to 99 to set the IP
address.
IP Address
*
Set the IP address for the TS.
Default Gateway
*
Set the default gateway.
Subnet Mask
*
Set the subnet mask.
When this box is not checked, the subnet mask is automatically assigned
based on the byte at the extreme left of the IP address.
Example:
IP address 172.16.200.185: “255.255.0.0” is set.
IP address 192.168.1.185: “255.255.255.0” is set.
Port No.
*
Set a port No. 1024 to 65535, except for 8001.
Send Timeout
Set a timeout period for transmitting macro commands SEND, EREAD or
EWRITE, or macro commands for MES.
Retrials
0 to 255
Set the number of retrials to be performed when a time-out occurs.
Memory Protect
Internal Memory
Memory Card Memory
Check either check box to write-protect the memory from computers or
other stations.