03-02
( Factory setting)
Setting Description
Function Number Setting Value
Enable
Disable
40
00
01
( Factory setting)
Setting Description
Function Number Setting Value
No
Yes
42
00
01
1-4. Auto Restart
Enable or disable automatic restart after a power interruption.
1-5. Room temperature sensor switching (Only for Wired remote controller)
The following settings are needed when use the control by
Wired remote controller temperature sensor.
( Factory setting)
Setting Description
Function Number Setting Value
A
B
C
D
44
00
01
02
03
1-6. Remote controller signal code
The indoor unit signal code can be changed. Select the appropriate signal code.
( Factory setting)
Setting Description
Function Number Setting Value
Operation/Stop mode
(Setting prohibited)
Forced stop mode
46
00
01
02
1-7. External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
* If setting value is "00" : Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is "01" : Room temperature is controlled by remote controller unit sensor.
* Auto restart is an emergency function such as for power outage etc. Do not attempt to
use this function in normal operation. Be sure to operate the unit by remote controller or
other external input device.
( Factory setting)
Setting Description
Function Number Setting Value
Disable
Enable
49
00
01
1-8. Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when
the outdoor unit is stopped during cooling operation.
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.