EasyManuals Logo

Fujitsu AOTG36LATT User Manual

Fujitsu AOTG36LATT
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #86 background imageLoading...
Page #86 background image
En-1
1. SAFETY PRECAUTIONS
Be sure to read this Manual thoroughly before installation.•
The warnings and precautions indicated in this Manual contain important information •
pertaining to your safety. Be sure to observe them.
Hand this Manual, together with the Operating Manual, to the customer. Request the •
customer to keep them on hand for future use, such as for relocating or repairing the
unit.
WARNING
Indicates a potentially or imminently hazardous situation
which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that may result in
minor or moderate injury or damage to property.
WARNING
•Theapplianceshallbeinstalled,operatedandstoredinaroomwithaoorarealarger
than 2.06 m
2
.
•Installationofthisproductmustbedonebyexperiencedservicetechniciansorprofes-
sional installers only in accordance with this manual. Installation by non-professional
or improper installation of the product might cause serious accidents such as injury,
waterleakage,electricshock,orre.Iftheproductisinstalledindisregardofthe
instructions in this manual, it will void the manufacturer’s warranty.
•Donotturnonthepoweruntilallworkhasbeencompleted.Turningonthepower
before the work is completed can cause serious accidents such as an electric shock
orare.
•Ifrefrigerantleakswhenyouareworking,ventilatethearea.Iftheleakingrefrigerant
isexposedtoadirectame,itmayproduceatoxicgas.
•Installationmustbeperformedinaccordancewithregulations,codes,orstandardsfor
electrical wiring and equipment in each country, region, or the installation place.
•Donotusemeanstoacceleratethedefrostingprocessortoclean,otherthanthose
recommended by the manufacturer.
•Theapplianceshallbestoredinaroomwithoutcontinuouslyoperatingignition
sources(forexample:openames,anoperatinggasapplianceoranoperating
electric heater.
•Donotpierceorburn.
•Beawarethatrefrigerantsmaynotcontainanodour.
CAUTION
•Readcarefullyallofsafetyinformationwritteninthismanualbeforeyouinstalloruse
the air conditioner.
•Installtheunitbyfollowinglocalcodesandregulationsinforceattheplaceof
installation, and the instructions provided by the manufacturer.
•Thisunitispartofasetconstitutinganairconditioner.Theunitmustnotbeinstalled
alone or be installed with non-authorized device by the manufacturer.
•Alwaysuseaseparatepowersupplylineprotectedbyacircuitbreakeroperatingonall
wires with a distance between contact of 3 mm for this unit.
•Toprotectthepersons,earth(ground)theunitcorrectly,andusethepowercable
combinedwithanEarthLeakageCircuitBreaker(ELCB).
•Theunitsarenotexplosionproof,andthereforeshouldnotbeinstalledinexplosive
atmosphere.
•Toavoidgettinganelectricshock,nevertouchtheelectricalcomponentssoonafter
thepowersupplyhasbeenturnedoff.Afterturningoffthepower,alwayswait5min-
utes or more before you touch the electrical components.
•Thisunitcontainsnouser-serviceableparts.Alwaysconsultexperiencedservice
technicians for reparing.
CAUTION
•Whenmovingorrelocatingtheairconditioner,consultexperiencedservicetechnicians
for disconnection and reinstallation of the unit.
•Donotplaceanyotherelectricalproductsorhouseholdbelongingsunderindoorunit
or outdoor unit. Condensation dripping from the unit might get them wet, and may
cause damage or malfunction of your property.
•Becarefulnottoscratchtheairconditionerwhenhandlingit.
•Afterinstallation,explaincorrectoperationtothecustomer,usingtheoperatingmanual.
Precautions for using R32 refrigerant
Thebasicinstallationworkproceduresarethesameasconventionalrefrigerant(R410A,
R22)models.
However,paycarefulattentiontothefollowingpoints:
Since the working pressure is 1.6 times higher than that of refrigerant R22 models,
some of the piping and installation and service tools are special. (See “2.1. Special
toolsforR32(R410A)”.)
Especially, when replacing a refrigerant R22 model with a new refrigerant R32 model,
alwaysreplacetheconventionalpipingandarenutswiththeR32andR410Apipingand
arenutsontheoutdoorunitside.
ForR32andR410A,thesamearenutontheoutdoorunitsideandpipecanbeused.
ModelsthatuserefrigerantR32andR410Ahaveadifferentchargingportthreaddiam-
eter to prevent erroneous charging with refrigerant R22 and for safety. Therefore, check
beforehand.[ThechargingportthreaddiameterforR32andR410Ais1/2inch.]
BemorecarefulthanR22sothatforeignmatter(oil,water,etc.)doesnotenterthe
piping.Also,whenstoringthepiping,securelysealtheopeningbypinching,taping,etc.
(HandlingofR32issimilartoR410A.)
CAUTION
1-Installation(Space)
That the installation of pipe-work shall be kept to a minimum.•
That pipe-work shall be protected from physical damage.•
The appliance shall not be installed in an unventilated space, if that space is smaller •
than 2.06 m
2
.
That compliance with national gas regulations shall be observed.•
That mechanical connections shall be accessible for maintenance purposes.•
In cases that require mechanical ventilation, ventilation openings shall be kept clear •
of obstruction.
Whendisposingoftheproductisused,bebasedonnationalregulations,properly•
processed.
2-Servicing
2-1 Service personnel
Anypersonwhoisinvolvedwithworkingonorbreakingintoarefrigerantcircuit•
shouldholdacurrentvalidcerticatefromanindustry-accreditedassessment
authority, which authorises their competence to handle refrigerants safely in accord-
ancewithanindustryrecognisedassessmentspecication.
Servicing shall only be performed as recommended by the equipment manufacturer. •
Maintenance and repair requiring the assistance of other skilled personnel shall be
carriedoutunderthesupervisionofthepersoncompetentintheuseofammable
refrigerants.
Servicing shall be performed only as recommended by the manufacturer.•
AIRCONDITIONER
WallMountedType
INSTALLATION MANUAL
Contents
1. SAFETYPRECAUTIONS .................................................................. 1
2. ABOUTTHEPRODUCT.................................................................... 3
3. GENERALSPECIFICATION ............................................................. 4
4. ELECTRICALREQUIREMENT ......................................................... 4
5. SELECTINGTHEMOUNTINGPOSITION ....................................... 4
6. INSTALLATIONWORK ..................................................................... 4
7. ELECTRICALWIRING ..................................................................... 7
8. FINISHING........................................................................................ 7
9. FRONTPANELREMOVALANDINSTALLATION ............................. 8
10. TESTRUN ......................................................................................... 8
11. REMOTECONTROLLERINSTALLATION ........................................ 9
12. OPTIONALKITINSTALLATION(OPTION) ....................................... 9
13. INSTALLATIONWORK ..................................................................... 9
14. SELECTINGTHEREMOTECONTROLLERSIGNALCODE ......... 10
15. FUNCTIONSETTING...................................................................... 10
16. CUSTOMERGUIDANCE ................................................................ 12
17. ERRORCODES .............................................................................. 12
PARTNo.9320456009
For authorized service personnel only.
R32
R32.
ASTG18KMCA_中型標準モデルLM系_R32_0724m.indd 1 2013/07/24 16:51:39

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOTG36LATT and is the answer not in the manual?

Fujitsu AOTG36LATT Specifications

General IconGeneral
BrandFujitsu
ModelAOTG36LATT
CategoryAir Conditioner
LanguageEnglish

Related product manuals