- (01 - 26) -
WALL MOUNTED TYPE
ASTG18-24KMCA
WALL MOUNTED TYPE
ASTG18-24KMCA
FUNCTION DETAILS
Functions
1) Filter sign
2) Room temperature control for cooling
3) Room temperature control for heating
4) Auto restart
5) Room temperature sensor switching
6) Remote controller custom code
7) External input control
8) Indoor unit fan control for energy saving for cooling
1) Filter sign
Select appropriate intervals for displaying the lter sign on the indoor unit according to the
estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
(
... Factory setting)
Setting description Function number Setting value
Standard (400 hours)
11
00
Long interval (1000 hours) 01
Short interval (200 hours) 02
No indication 03
2) Room temperature control for cooling
Depending on the installed environment, correction of the room temperature sensor may be
required.
Select the appropriate control setting according to the installed environment.
(
... Factory setting)
Setting description Function number Setting value
Standard
30
00
Slightly lower control 01
Lower control 02
Higher control 03
3) Room temperature control for heating
Depending on the installed environment, correction of the room temperature sensor may be
required.
Select the appropriate control setting according to the installed environment.
(
... Factory setting)
Setting description Function number Setting value
Standard
31
00
Lower control 01
Slightly Higher control 02
Higher control 03