03-01
3-1. FUNCTION SETTING
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control,
in accordance with the installed condition.
After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value.
Settings will not be changed if invalid numbers or setting values are selected.
3-1-1 INDOOR UNIT
( Factory setting)
Setting Description
Function Number Setting Value
Standard (400 hours)
Long interval (1000 hours)
Short interval ( 200 hours)
No indication
11
00
01
02
03
1-1. Filter Sign
Select appropriate intervals for displaying the fi lter sign on the indoor unit according to the
estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
( Factory setting)
Setting Description
Function Number Setting Value
Standard
Slightly lower control
Lower control
Higher control
30
00
01
02
03
1-2. Room temperature control for cooling
Depending on the installed environment, correction of the room temperature sensor may
be required. Select the appropriate control setting according to the installed environment.
( Factory setting)
Setting Description
Function Number Setting Value
Standard
Lower control
Slightly higher control
Higher control
31
00
01
02
03
1-3. Room temperature control for heating
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be changed as shown in the table below.