En-11
Selecting the Function Number and Setting Value
[Cool model]
(1) Press the TEMP. (
/ ) buttons to select the func-
tion number.(Press the ECONOMY button to switch
betweentheleftandrightdigits.)
(2) Press the POWERFULbutton to proceed to setting
value.(PressthePOWERFULbuttonagaintoreturnto
thefunctionnumberselection.)
(3) PresstheTEMP.(
/ )buttonstoselectthesetting
value.(PresstheECONOMYbuttontoswitchbetween
theleftandrightdigits.)
(4) Press the MODE button, and START/STOP button, in
theorderlistedtoconrmthesettings.
(5) PresstheRESETbuttontocancelthefunctionsetting
mode.
(6) Aftercompleting theFUNCTION SETTING,be sureto
turn off the power and turn it on again.
Function Number
Setting
Value
CAUTION
Afterturningoffthepower,wait30secondsormorebeforeturningonitagain.The
function setting does not become active unless the power is turned off then on again.
Filter sign
Selectappropriateintervalsfordisplayingtheltersignontheindoorunitaccordingtothe
estimated amount of dust in the air of the room.
Iftheindicationisnotrequired,select“Noindication”(03).
(♦...Factorysetting)
Setting Description
Function
Number
Setting Value
Standard(400hours)
11
00
Longinterval(1,000hours) 01
Shortinterval(200hours) 02
♦ Noindication 03
Room temperature control for cooling
Dependingon theinstalledenvironment,correctionoftheroomtemperaturesensormay
be required. Select the appropriate control setting according to the installed environment.
(♦...Factorysetting)
Setting Description
Function
Number
Setting Value
♦ Standard
30
00
Slightly lower control 01
Lower control 02
Higher control 03
Room temperature control for heating [Reverse cycle model only]
Dependingon theinstalledenvironment,correctionoftheroomtemperaturesensormay
be required. Select the appropriate control setting according to the installed environment.
(♦...Factorysetting)
Setting Description
Function
Number
Setting Value
♦ Standard
31
00
Lower control 01
Slightly higher control 02
Higher control 03
Auto restart
Enable or disable automatic restart after a power interruption.
(♦...Factorysetting)
Setting Description
Function
Number
Setting Value
♦ Enable
40
00
Disable 01
*Autorestartisan emergencyfunction suchas forpoweroutageetc.Donotattempt to
use this function in normal operation. Be sure to operate the unit by remote controller or
otherexternalinputdevice.
Room temperature sensor switching
(Onlyforwirelessremotecontroller)
WhenusingtheWiredremotecontrollertemperaturesensor,changethesettingto“Both”
(01).
(♦...Factorysetting)
Setting Description
Function
Number
Setting Value
♦ Indoor unit
42
00
Both 01
00:Sensorontheindoorunitisactive.
01:Sensorsonbothindoorunitandwiredremotecontrollerisactive.
Remote controller signal code
(Onlyforwirelessremotecontroller)
The indoor unit signal code can be changed. Select the appropriate signal code.
(♦...Factorysetting)
Setting Description
Function
Number
Setting Value
♦ A
44
00
B 01
C 02
D 03
External input control
“Operation/Stop”modeor“Forcedstop”modecanbeselected.
(♦...Factorysetting)
Setting Description
Function
Number
Setting Value
♦ Operation/Stopmode
46
00
(Settingforbidden) 01
Forced stop mode 02
Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when
the outdoor unit is stopped during cooling operation.
(♦...Factorysetting)
Setting Description
Function
Number
Setting Value
♦ Disable
49
00
Enable 01
00:Whentheoutdoorunitisstopped,theindoorunitfanoperatescontinuouslyfollowing
the setting on the remote controller.
01:Whentheoutdoorunitisstopped,theindoorunitfanoperatesintermittentlyatavery
low speed.
Setting record
Record any changes to the settings in the following table.
Setting Description Setting Value
Filter sign
Room temperature control for cooling
Room temperature control for heating
Autorestart
Room temperature sensor switching
Remote controller signal code
Externalinputcontrol
Indoor unit fan control for energy saving for cooling
AftercompletingtheFUNCTION SETTING, be suretoturn off thepowerandturn it on
again.