EasyManua.ls Logo

Fujitsu Eternus DX600 S3 - Chapter 1 ETERNUS DX Installation; Installation Specifications; Eternus Dx500 S3; Table 1.1 ETERNUS DX500 S3 Installation Specifications

Fujitsu Eternus DX600 S3
51 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 1
ETERNUS DX Installation
This chapter explains the installation of the ETERNUS DX.
1.1 Installation Specifications
1.1.1 ETERNUS DX500 S3
The following table shows the installation specifications of the ETERNUS DX500 S3.
Table 1.1 ETERNUS DX500 S3 Installation Specifications
Item
ETERNUS DX500 S3
Dimensions
(W ´ D ´ H)
Controller enclosure
482 ´ 805 ´ 133mm (3U)
Drive enclosure 2.5" type
482 ´ 540 ´ 88mm (2U)
3.5" type
482 ´ 560 ´ 88mm (2U)
High-density
type
482 ´ 980 ´ 176mm (4U)
Power distribution unit 1U
435 ´ 148 ´ 38mm
2U
(485 ´ 280 ´ 43mm) ´ 2 (*1)
Maximum weight
(approx.)
Controller enclosure 54kg
Drive enclosure (*2) 2.5" type 35kg
3.5" type 35kg
High-density
type
95kg
Power distribution unit 1U 2kg
2U
(6kg) ´ 2 (*1)
Power Voltage AC 100 – 120V, AC 200 – 240V
Phase Single
Frequency 50Hz/60Hz
Maximum power
consumption
Controller enclosure AC 100 – 120V 650W (660VA)
AC 200 – 240V 760W (770VA)
Drive enclosure
(*2)
2.5" type AC 100 – 120V 430W (440VA)
AC 200 – 240V 430W (440VA)
3.5" type AC 100 – 120V 340W (350VA)
AC 200 – 240V 340W (350VA)
High-density
type
AC 100 – 120V 1,300W (1,320VA)
AC 200 – 240V 1,300W (1,320VA)
11
FUJITSU Storage ETERNUS DX500 S3/DX600 S3 Disk storage system Site Planning Guide
Copyright 2014 FUJITSU LIMITED
P3AM-7712-05ENZ0

Table of Contents

Other manuals for Fujitsu Eternus DX600 S3