● Power Distribution Units (2U)
•
Power distribution unit (AC200-240V, 2U, 12 outlets)
There are 12 outlets.
•
Power distribution unit (AC200-240V, 2U, 16 outlets)
There are 16 outlets.
Figure 1.12 Power Distribution Units (2U)
Twelve or sixteen outlets
Two inlets
● Power Distribution Unit (AC200-240V, 1U, 4 Outlets)
Table 1.10 Power Distribution Unit (AC200-240V, 1U, 4 Outlets) Specifications
Outlet
Inlet
Voltage rating/current
rating
Socket type
(Socket)
Plug type
Socket type
(Socket)
Cable length
IEC60320-C13 NEMA L6-15P NEMA L6-15R 4.0m Rating: 250V 10A
(Normal usage rating:
8A)
● Power Distribution Unit (AC200-240V, 2U, 12 Outlets)
Table 1.11 Power Distribution Unit (AC200-240V, 2U, 12 Outlets) Specifications
Outlet
Inlet
Voltage rating/current
rating
Socket type
(Socket)
Plug type
Socket type
(Socket)
Cable length
IEC60320-C13 NEMA L6-20P NEMA L6-20R 4.0m Rating: 250V 20A
(Normal usage rating:
16A)
Chapter 1 ETERNUS DX Installation
1.7 Outlet/Socket Specifications
29
FUJITSU Storage ETERNUS DX500 S3/DX600 S3 Disk storage system Site Planning Guide
Copyright 2014 FUJITSU LIMITED
P3AM-7712-05ENZ0