1.7.1 Specifications for Optional Power Supply Products
This section explains the specifications of optional power cords and power related optional products.
For power distribution units, the number of outlets that are required to connect the controller enclosure and
drive enclosures should be taken into consideration, and the most appropriate power distribution units
should then be selected.
When an existing power socket is used, make sure that the plug type of the power distribution unit fits the
existing power socket and that the power supply facility is able to provide sufficient power to the system. If
the plug type does not fit the power socket, electrical work to change the power socket is required. This elec-
trical work must be performed in compliance with the electrical codes of the nation, the municipality, or the
region.
■
Power Cords
● AC200V Power Cords (for the EMEA&I Region)
AC200V power cords are used to connect devices to the IEC60320-C13 power socket type. These power cords
can be used if the specifications of the connection device allow AC200V.
Table 1.5 Specifications for AC200V Power Cords (for the EMEA&I Region)
Usage Plug type
Socket type
(Socket)
Cable length
Voltage rating/current
rating
Used for connection be-
tween the ETERNUS DX
and the socket
(IEC60320-C13 n
IEC60320-C14G)
IEC60320-C14G IEC60320-C13 2.5m 250V 10A
● Power Cords Supplied with the ETERNUS DX (for Regions Other than EMEA&I)
AC200V power cords are used to connect devices to the NEMA L6-15R power socket type. These power cords
can be used if the specifications of the connection device allow AC200V.
Table 1.6 Specifications for AC200V Power Cords (for Regions Other than EMEA&I)
Usage
Plug type
Socket type
(Socket)
Cable length
Voltage rating/current
rating
Used for connection be-
tween the ETERNUS DX
and the socket
(IEC60320-C13 n
NEMA L6-15P)
NEMA L6-15P NEMA L6-15R 4.0m Rating: 250V 10A
(Normal usage rating:
8A)
Chapter 1 ETERNUS DX Installation
1.7 Outlet/Socket Specifications
27
FUJITSU Storage ETERNUS DX500 S3/DX600 S3 Disk storage system Site Planning Guide
Copyright 2014 FUJITSU LIMITED