1.6.2 Installation Methods
•
Perform one of the following rack installation methods to ensure the safe use of an ETERNUS DX that is
installed in a rack:
-
To secure a rack, use a rack without stabilizers and secure it to the building with the leveling feet.
-
If a rack is not to be secured, make sure to use a rack with stabilizers and use these stabilizers to prevent
the rack from toppling over.
•
Which installation method should be used depends on the installation location, the floor conditions, and
the type of racks that are to be used. Contact your installation contractor for more details regarding instal-
lation and how the installation should actually be performed.
The following figure shows the dimensions of the location on a floor in which a rack is secured.
Figure 1.10 Dimensions of the Location on a Floor in which a Rack is Secured
919mm (pillar)
733mm (caster)
Front Rear
523mm
(caster)
: Caster
: Pillar
: Cable slot
350mm
570mm
(pillar)
175mm
700mm
1,050mm
95mm
826mm
65mm
89
mm
47mm
140mm
1,013 mm
1.6.3 Load Bearing Capacity for Floors
Make sure that the following relationship between the load bearing capacity of the floor and the weight of
the ETERNUS DX is maintained.
(Load bearing capacity of the floor) > (ETERNUS DX weight ¸ Installation area that includes service
areas)
If the condition above is not satisfied, additional measures are required to ensure sufficient load bearing ca-
pacity.
Contact your installation contractor for details about the necessary measures that must be taken.
Chapter 1
ETERNUS DX Installation
1.6 Installation Environment
25
FUJITSU Storage ETERNUS DX500 S3/DX600 S3 Disk storage system Site Planning Guide
Copyright 2014 FUJITSU LIMITED