Figure 2.10 Unit Installation Area
ETERNUS DX
(1) (2)
(3)
(4)
Rear door of the rac
k
Front door of the rack Rack pillars
Rack rails
Table 2.3 Specifications for the Unit Installation Area
Specification
Condition
Conditions when high-density drive
enclosures are installed
(1) Rack front space
(Space between the fixed part of the ETERNUS DX
on the front side and the front of the rack)
40mm or more 80mm or more
(2) Mount bracket length
(Size between each end of the front and rear rack
pillars)
685mm or more
775mm or less
685mm or more
750mm or less
(3) Rack space
(Space between the fixed part of the ETERNUS DX
on the front side and the rear of the rack)
890mm or more 915mm or more
(4) Rack mount kit installation area 482mm or more
(recommended)
490mm or more
Placement Requirements
When determining service areas, refer to the manual of the rack that is to be used.
Make sure to perform the installation according to the placement requirements described in "1.1 Installation
Specifications" (page 11) and "1.6 Installation Environment" (page 24).
Chapter 2
Rack Installation Specifications
2.2 Installable Racks
49
FUJITSU Storage ETERNUS DX500 S3/DX600 S3 Disk storage system Site Planning Guide
Copyright 2014 FUJITSU LIMITED
P3AM-7712-05ENZ0