Power Distribution Unit (AC200-240V, 2U, 16 Outlets)
Table 1.12 Power Distribution Unit (AC200-240V, 2U, 16 Outlets) Specifications
Outlet Inlet
Voltage rating/current
rating
Socket type
(Socket)
Plug type
Socket type
(Socket)
Cable length
IEC60320-C13 NEMA L6-30P NEMA L6-30R 4.0m Rating: 250V 30A
(Normal usage rating:
24A)
1.7.2 Required Number of Outlets/Sockets
The number of power outlets/sockets required to install the ETERNUS DX depends on the number of drive
enclosures and power distribution units.
It is recommended that the power cords of the drive enclosures are connected to the power distribution units
that are installed in the same rack. Secure the necessary number of power outlets within the same rack to
avoid connecting power cords to power outlets in different racks. It may be necessary to purchase additional
power distribution units depending on the installation locations of enclosures.
Without Power Distribution Units
Two power sockets are required for every controller enclosure, 2.5" type drive enclosure, and 3.5" type drive
enclosure.
Four power sockets are required for each high-density drive enclosure.
With Power Distribution Units
Two power sockets are required for each power distribution unit.
Chapter 1
ETERNUS DX Installation
1.7 Outlet/Socket Specifications
30
FUJITSU Storage ETERNUS DX500 S3/DX600 S3 Disk storage system Site Planning Guide