Fujitsu Eternus DX600 S3 - Figure 1.11 Power Distribution Units (1 U); Table 1.7 Specifications for AC125 V Power Cords (for Regions Other than EMEA&I); Table 1.8 Specifications for Power Cords (for Regions Other than EMEA&I); Table 1.9 Required Number of Outlets and Sockets to Install Power Distribution Units

Fujitsu Eternus DX600 S3
51 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AC125V Power Cords (for Regions Other than EMEA&I)
AC125V power cords are used to connect devices to the NEMA 5-15R power socket type. These power cords
can be used if the specifications of the connection device allow AC100V.
Table 1.7 Specifications for AC125V Power Cords (for Regions Other than EMEA&I)
Usage Plug type
Socket type
(Socket)
Cable length
Voltage rating/current
rating
Used for connection be-
tween the ETERNUS DX
and the socket
(IEC60320-C13 n
NEMA 5-15P)
NEMA 5-15P NEMA 5-15R 3.0m Rating: 125V 13A
(Normal usage rating:
10A)
AC100V and AC200V Power Cords (for Regions Other than EMEA&I)
AC100V/200V power cords are used to connect devices to the IEC60320-C13 power socket type. These power
cords can be used to connect devices with the AC100V and AC200V specifications.
Table 1.8 Specifications for Power Cords (for Regions Other than EMEA&I)
Usage Plug type
Socket type
(Socket)
Cable length
Voltage rating/current
rating
Used for connection be-
tween the ETERNUS DX
and the socket
(IEC60320-C13 n
IEC60320-C14)
IEC60320-C14 IEC60320-C13 0.5m
1.0m
1.5m
3.0m
Rating: 250V 10A
(Normal usage rating:
8A)
Power Distribution Units (Only for Regions Other than EMEA&I)
There are four types of power distribution units. The size and number of outlets are different for each type.
Table 1.9 Required Number of Outlets and Sockets to Install Power Distribution Units
Power distribution unit
Number of sockets
Outlets Inlets
Power distribution unit (AC200-240V, 1U, 4 outlets) 4 2
Power distribution unit (AC200-240V, 2U, 12 outlets) 12 2
Power distribution unit (AC200-240V, 2U, 16 outlets) 16 2
Power Distribution Units (1U)
There are four outlets.
Figure 1.11 Power Distribution Units (1U)
Two inlets
Four outlets
Chapter 1
ETERNUS DX Installation
1.7 Outlet/Socket Specifications
28
FUJITSU Storage ETERNUS DX500 S3/DX600 S3 Disk storage system Site Planning Guide
Copyright 2014 FUJITSU LIMITED
P3AM-7712-05ENZ0