Item ETERNUS DX600 S3
Maximum
amount of ex-
haust air
Controller enclosure
6.2m
3
/min
Drive enclosure (*3) 2.5" type
4.0m
3
/min
3.5" type
4.0m
3
/min
High-density
type
12.0m
3
/min
Environmental
conditions
Temperature Operating 10 – 40°C
Not operating 0 – 50°C
Shipping -40 – 60°C
Temperature gradient 15°C/Hr or less
Humidity Operating 20 – 80%RH
Not operating 8 – 80%RH
Shipping 8 – 90%RH
Humidity gradient 30%/day or less
Maximum wet bulb temperature 29°C
Altitude above sea level 0 – 3000m
Airborne dust
0.15mg/m
3
or less
Gas concentration tolerance level Cl
2
: 3.4ppb or less, H
2
S: 7.1ppb or less,
SO
2
: 37ppb or less, NH
3
: 420ppb or less,
NO
2
: 52ppb or less, O
3
: 5ppb or less,
HCl: 6.6ppb or less, HF: 3.6ppb or less
Oil vapor
0.2mg/m
3
or less
Seawater (salt corrosion) If the ETERNUS DX is installed on the ocean or
premises within 0.5km from the coast, necessary
measures must be taken to prevent salt corro-
sion.
Vibration limit Operating 400gal
Not operating 1,000gal
Noise emission
(*3)
Sound Pressure Level 54dB (A)
Sound Power Level 7.2B
*1: A 2U power distribution unit is composed of two 1U power distribution units.
*2: These values are for each drive enclosure when 24 drives are installed in a 2.5" type drive enclosure, 12
drives are installed in a 3.5" type drive enclosure, or 60 drives are installed in a high-density drive en-
closure.
*3: These values are measured when a single controller enclosure and four drive enclosures are configured
in an environment in which the temperature is 23 ± 2 °C.