RX200 S5 Operating Manual 39
Hardware installation Installing/removing the server in/from the rac
4.2 Installing/removing the server in/from the
rack
V CAUTION!
● Follow the safety instructions in chapter "Important information" on
page 25 and section section "Notes on installing in the rack" on
page 34.
● At least two people are needed to position the server into/out of the
rack.
● The rack can tip over when more than one unit is removed.
● The server may not occupy the top height unit of the rack (38 HU/42
HU PRIMECENTER Rack and/or DataCenter Rack), as otherwise
boards or fans cannot be replaced even with the plug-in module fully
extended.
4.2.1 Rack system requirements
The rack systems from Fujitsu Technology Solutions, PRIMECENTER Rack
and DataCenter Rack, support the installation of PRIMERGY servers.
Installation in most current rack systems from other manufacturers (3rd party
racks) is also supported.
To accommodate the ventilation concept and ensure proper ventilation, any
unused areas in the rack must be sealed using dummy covers.
The power is supplied via the multiple socket outlets fitted in the rack.
PRIMECENTER/DataCenter Rack
The main features of the rack systems from Fujitsu Technology Solutions are as
follows:
– Support systems that can be mounted without tools
The support systems have a linear alignment feature to ensure that they can
be adjusted to different rack depths.
– Enhanced cable management in the lateral rack area