102
Advent Commercial Fire System
Contact ID Codes and Event Types
Use Table B.8 for determining event types and CID codes.
Note
Items in grey are not supported.
Table B.8 Contact ID Codes
Description
Specific
Type
Contact ID
Code
Associated
Zone Type
Alarms
(General Types 1–Alarm, 2–Alarm Cancel, 3–Alarm Restoral)
Note
All alarm cancels are reported as CID code 406
*Advent has a defined level that reports “silent burglary” (CID
146). This will be used in place of the defined event code at the
appropriate level.
Unspecified 0 140
Fire 1 110 26, 90
Fire Panic 2 115 60(B), 62,
Touchpad
Panics
Police 3 130 8, 9, 30*, 60(A),
61*, 64*, 75-79*
Police Panic 4 120 0, 1,
Touchpad Panics
Medical 5 100 4-7, Touchpad Panics
Medical Panic 6 101 54-57, Touchpad Panics
Auxiliary 7 140
Auxiliary Panic 8 100 4-7,
Touchpad Panics
Tamper 9 144 63*, 65*, 66*, 85,
Any Zone
No Activity 10 102
Suspicion 11 122 2, 3, 58, 73, 74
Buddy 12 140
Low Temperature Limit 13 159
High Temperature Limit 14 158
Keystroke Violation 15 145
Duress 16 121
Exit Fault 17 374
Explosive Gas 18 151 34, 67
Carbon Monoxide 19 162 68
Environmental 20 150 29
Latchkey 21 642
Equipment Tamper 22 137
Holdup 23 122 2, 3, 58, 73, 74
Sprinkler 24 113 82
Heat 25 114 81
Siren Tamper 26 137
Smoke 27 111 80
Repeater 28 144 63*, 65*, 66*, 85,
Any Zone
Fire Pump Activated 29 110 26, 90
Fire Pump Failure 30 140
Fire Gate Valve 31 140
Low CO2 Pressure 32 140
Low Liquid Pressure 33 140
Low Liquid Level 34 140
Entry Exit Intrusion (Police) 35 134 10-12*
Perimeter Intrusion (Police) 37 131 13*
Interior Intrusion (Police) 38 132 14-20*
Fire Trouble
(General Types 4–Zone Trouble Fire, 5–Zone Trouble Restoral
Fire)
Unspecified 0 373
Hardwire Trouble 1 373
Ground Fault 2 310
Device Trouble 3 373
RF Supervisory 4 381
RF Low Battery 5 384
Tamper 6 383
Suspected Sensor Failure 7 373
Partial Obscurity 8 386
RF Jam 9 373
Zone AC Failure 10 373
Zone Low Battery 11 373
NAC Trouble 12 373
Analog Zone Trouble 13 373
Fire Supervisory Trouble 14 200 96
Pump Failure 15 206 91
Gate Valve Closed 16 203 92
CO2 Pressure 17 202 93
Liquid Pressure 18 201 94
Liquid Level 19 204 95
Non-Fire Trouble
(General Types 6–Zone Trouble Non Fire, 7–Zone Trouble
Restoral Non Fire)
Unspecified 0 380
Hardwire Trouble 1 380
Ground Fault 2 310
Device Trouble 3 380
RF Supervisory 4 381
RF Low Battery 5 384
Table B.8 Contact ID Codes (Continued)
Description
Specific
Type
Contact ID
Code
Associated
Zone Type