26
Advent Commercial Fire System
Partitions/Zones
Announce and Display Zone Text with Chime
xx110 (Partitions-Zones)
(Default = off) If on, zone text will be announced over speakers
and displayed on touchpads whenever a chime sounds (the sensor
is open or closed).
Note
Only partition/area 1 has voice capabilities.
To turn Announce and Display Zone Text with
Chime On/Off:
Once the item number has been entered, enter 1 to turn the
setting on or 0 to turn it off. Press ƒ to apply the new setting.
Chime On Zone Restoral
xx111 (Partitions-Zones)
(Default = off) If on, a chime will sound whenever a zone is
restored.
To turn Chime on Zone Restoral On/Off:
Once the item number has been entered, enter 1 to turn the
setting on or 0 to turn it off. Press ƒ to apply the new setting.
Key or Code Needed for Special Fire Touchpad Keys
xx082 (Partitions-Zones)
(Default = on) If on, then a key or code must be used before using
the special panic keys (on fire touchpad) to acknowledge an
alarm, silence an alarm, or perform a fire alarm drill. If off, then
no key or code is required to use the special panic keys.
To turn Key or Code Needed for Special Fire
Touchpad Keys On/Off:
Once the item number has been entered, enter 1 to turn the
setting on (key or code required) or 0 to turn it off. Press ƒ to
apply the new setting.
Zone Test Time Out
xx011 (Partitions-Zones)
(Default = 30 minutes) Enter the length of time (in minutes) after
which a zone test automatically times out (ends).
To set the Zone Test Time Out:
Once the item number has been entered, enter the number of
minutes (5–120) before a zone test ends and press ƒ.
Disarm Key
Arm Key
Lights Key
Star Key
Lights/Star Keys
Arm Level 2
Arm Level 3
Arm/Star Keys
Disarm/Lights Keys
xx057, xx058, xx059, xx060, xx061, xx063, xx064, xx065,
xx066 (Partitions-Zones)
(Defaults = Unlock-4, Lock-9, Lights-15, Star-12, Light/Star-3,
Level 2-6, Level 3-5, Arm/Star-16, Disarm/Lights-16) These
settings allow you to specify how the system behaves when
specific keychain touchpad button or button combinations are
pressed.
Special Action Assignments:
0- not used
1- not used
2- not used
3- auxiliary panic (only used for item no. xx061)
4- arm to level 1
5- arm to level 2
6- arm to level 3
7- arm to special level 4
8- arm to special level 5
9- arm to closed level
10- arm to closed level with no delay
11- arm to closed level with Latchkey
12- increment arming level from 0 to 1, 1 to 2, or 2 to 3
only
13- turn all* lights on
14- turn all* lights off
15- toggle all* lights
16- do nothing
* all lights having the first (of two) house codes in the partition.
Specifying Keychain Touchpad Button Action:
1. Once the desired item number has been entered, enter the
special action assignment number (3–16) from the above
list.
2. Press
ƒ to apply the new setting.
Enable Auxiliary/Medical Panic Keys
xx086 (Partitions-Zones)
(Default = on) Choose whether or not to enable the Auxiliary
panic buttons on non-fire touchpads. If enabled, when a user
presses and holds the Auxiliary panic buttons or presses them
twice, an auxiliary or medical alarm is generated. See Auxiliary/
Medical Assignments setting (xx084).
Turning Enable Auxiliary/Medical Panic Keys On/
Off:
Once the item number has been entered, enter 1 to turn the
setting on (enabled) or 0 to turn it off. Press ƒ to apply the new
setting.