Advent Commercial Fire System
Print Partition/Area Events
xx091 (Partitions-Reporting)
(Default = on) If on, the panel will print partition/area events on a
local printer.
To Print Partition/Area Events:
Once the item number has been entered, enter 1 (on) to enable
printing of partition/area events or 0 (off) to disable printing of
partition/area events. Press ƒ to apply the new setting.
Delay Between Generated Panic Alarm and Alarm
Reporting
xx012 (Partitions-Reporting)
(Default = 05 seconds) This setting allows you to specify the
length of time (in seconds) between the time a panic alarm
condition is detected, and a panic report is sent to the central
station. This allows users time to cancel a false alarm.
Note
If Cancel Event Cancels Report setting (xx089) is set to
off, this setting will have no affect.
Specifying the Delay Between Generated Panic
Alarm and Alarm Reporting:
Once the item number has been entered, enter the number of
seconds (1–120) you wish the panel to wait before sending a
panic report. Press ƒ to apply the new setting.
Delay Between Generated Standard Alarm and Alarm
Reporting
xx013 (Partitions-Reporting)
(Default = 05 seconds) This setting allows you to specify the
length of time (in seconds) between the time a non-panic and non-
fire alarm condition is detected, and a report is sent to the central
station. This allows users time to cancel a false alarm.
Note
If Cancel Event Cancels Report setting (xx089) is set to
off, this setting will have no affect.
Specifying the Delay Between Generated Standard
Alarm and Alarm Reporting:
Once the item number has been entered, enter the number of
seconds (1–120) you wish the panel to wait before sending a
report. Press ƒ to apply the new setting.
Delay Between Generated Fire Alarm and Alarm
Reporting
xx014 (Partitions-Reporting)
(Default = 0 minutes) This setting allows you to specify the length
of time (in minutes) between the time a fire alarm condition is
detected, and a report is sent to the central station. This allows
users time to cancel a false alarm.
Note
If Cancel Event Cancels Report setting (xx089) is set to
off, this setting will have no affect.
Specifying the Delay Between Generated Fire
Alarm and Alarm Reporting:
Once the item number has been entered, enter the number of
minutes (0–15) you wish the panel to wait before sending a
report. Press ƒ to apply the new setting.
Second Fire Alarm Ends Reporting Delay
xx090 (Partitions-Reporting)
(Default = on) If on, and a fire report delay is in progress, a
second fire alarm condition will end the delay between generated
fire alarm and alarm reporting (xx014), immediately sending a
report to the central station.
Programming Second Fire Alarm Ends Reporting
Delay:
Once the item number has been entered, enter 1 to turn the
setting on (second alarm ends delay) or 0 to turn it off. Press ƒ
to apply the new setting.
Second Intrusion Causes Report
xx077 (Partitions-Reporting)
(Default = off) If on, the first trip of an intrusion zone causes a
local police alarm. A second trip (different intrusion zone) within
four minutes generates a report. If off, the first trip of an intrusion
zone generates both an alarm and report.
To set the Second Intrusion Causes Report:
Once the item number has been entered, enter 1 to turn the
setting on or 0 to turn it off. Press ƒ to apply the new setting.
Generate Restoral Reports for Reporting Zone Types
xx112 (Partitions-Reporting)
(Default = off) If on, restoral reports are generated for all
reporting zone types (which require restoral). If off, the zone type
definition dictates whether on not a restoral report is generated.
To turn Generate Restoral Reports for Reporting
Zone Types On/Off:
Once the item number has been entered, enter 1 to turn the
setting on or 0 to turn it off. Press ƒ to apply the new setting.