AF-600 3-
phase
Recommended fuse
size
Recommended max
fuse
[kW]/[HP]
0.75/1 gG-20 gG-32
1.5/2
2.2/3
3.7/5
5.5/7.5
7.5/10
11/15 gG-50 gG-80
15/20
18.5/25
22/30 gG-80 gG-100
30/40
37/50 gG-125 gG-160
45/60
55/75
75/100 aR-250 aR-250
90/125
110/150 gG-300 gG-300
132/200 gG-350 gG-350
160/250 gG-400 gG-400
200/300 gG-500 gG-500
250/350 gG-630 gG-630
315/450 aR-700 aR-700
355/500
aR-900 aR-900400/550
450/600
500/650
aR-1600 aR-1600
560/750
630/900
aR-2000 aR-2000
710/1000
800/1200
aR-2500 aR-2500
1000/1350
Table 12.8 380–480 V, IP55/Nema 12 and IP66/Nema 4X
AF-600 3-
phase
Recommended fuse
size
Recommended max
fuse
[kW]/[HP]
0.75/1
gG-10 gG-25
1.5/2
2.2/3
3.7/5
5.5/7.5
gG-16 gG-32
7.5/10
11/15
gG-35 gG-6315/20
18.5/25
22/30
gG-63 gG-125
30/40
37/50
45/60
gG-100 gG-150
55/75
75/100
aR-250 aR-250
90/125
Table 12.9 525–600 V, IP20/Open Chassis
AF-600 3-
phase
Recommended fuse
size
Recommended max
fuse
[kW]/[HP]
0.75/1
gG-16 gG-32
1.5/2
2.2/3
3.7/5
5.5/7.5
7.5/10
11/15
gG-35 gG-8015/20
18.5/25
22/30
gG-50 gG-100
30/40
37/50
gG-125 gG-160
45/60
55/75
aR-250 aR-25075/100
90/125
Table 12.10 525–600 V, IP55/Nema 12