152 GE INFORMATION D20MX INSTRUCTION MANUAL
APPENDIX E: SECURE CONNECTION FOR LOGICLINX
NOTE
The Port Number may be any unused port number on the D20MX between 1 and
65535.
Result: The LogicLinx configuration appears as shown in the following screen.
2. Generate and synchronize this configuration to the target D20MX.
PuTTY configuration
To establish a secure tunnel using PuTTY:
1. Start PuTTY.
2. In the PuTTY Configuration dialog box, select Connection > SSH > Tunnels.
2.1. Under Port forwarding leave Local ports and Remote ports… unchecked.
2.2. Under Add new forwarding port: in the Source Port box type 1100, or any free
TCP port number on your PC.
2.3. In the Destination box, type the IP address 127.0.0.1:1100, where 1100 is the
port number set in the LogicLinx configuration (refer to step 1 in the: “LogicLinx
(B082-0N) configuration” section).
2.4. Click the IPv4 radio button.
Result: The PuTTY Configuration dialog box appears as in the following screen: