5-250 F60 Feeder Protection System GE Multilin
5.7 CONTROL ELEMENTS 5 SETTINGS
5
Figure 5–116: AUTORECLOSURE SCHEME LOGIC (Sheet 2 of 2)
SHOT COUNTER
FLEXLOGIC OPERANDS
FLEXLOGIC OPERAND
To
Sheet 1
Shot Count = MAX
ACTUAL VALUE
FLEXLOGIC OPERAND
Shot cnt = 4
AR1 SHOT CNT = 4
AR
1 SHOT CNT = 2
AR
1 SHOT CNT = 3
AR
1 SHOT CNT = 1
AR
1 SHOT CNT = 0
Increment
shot
counter
Shot cnt = 2
Shot cnt = 1
Shot cnt = 0
Reset shot
counter
Shot cnt = 3
AUTORECLOSE 1
SHOT COUNT: 0(1,2,3,4)
AR
1 CLOSE
AND
AND
AND
AND
AND
AND
AND
AND
100 ms
AND
OR
OR
OR
OR
OR
OR
OR
OR
SETTING
SETTING
SETTING
SETTING
SETTING
AR1 RESET TIME:
AR1 MAX NUMBER
OF SHOTS:
AR1 REDUCE MAX TO 1:
AR1 REDUCE MAX TO 2:
AR1 REDUCE MAX TO 3:
MAX = 1
Off = 0
Off = 0
Off = 0
MAX = 2
MAX = 3
MAX = 4
Close
Bkr is Closed
AR Initiate
LO
Reset from LO
To
Sheet 1
R
S
Latch
O
827082A7.CDR