MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 88 of 92
Table E-1: Main Tank: Gas Level Alarms
1) Set alarms to the following only if the measurements taken are LESS THAN the above values.
(C2H2 is set slightly higher to avoid spurious alarms)
* To avoid spurious alarms on the DGA 900, C2H2 Caution and Alarm limits should be set no lower than 2
and 3 ppm respectively.
2) Set alarms to the following only if the measurements taken are ABOVE the IEEE Condition 1 values.
Measured Value * yyy% = ppm caution/alarm value)
Note: The values cited in this table assume that no previous tests on the transformer for dissolved
gas analysis have been made or that no recent history exists. If a previous analysis exists, it should
be reviewed to determine if the situation is stable or unstable.
Note: See the example in Section E.8 at the end of this Appendix.
E.4 Main Tank: Gas Rate Of Change Alarms
Set the Rate of Change (ROC) alarms to the following values listed in Table E-2 for the most
critical gases:
▪ Daily Rate of Change (ROC) alarms – if oil volume is unknown
Table E-2: ROC alarms (key gas values)
▪ Daily Rate Of Change (ROC) alarms – if oil volume or weight is known
If the oil volume is known, the severity of defects based on ROC depends on the volume (or
weight) of oil contained in the transformer. For instance, a 1 ppm/day gas increase in a
large transformer (80,000 l oil) means a ROC of 80 ml/day of such gas. In a smaller