GE Multilin G60 Generator Protection System 4-29
4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE
4
ting password has been entered via the any external communications interface three times within a 3-minute time span, the
REMOTE ACCESS DENIED FlexLogic™ operand will be set to “On” and the G60 will not allow settings or command access
via the any external communications interface for the next five minutes.
In the event that an incorrect Command or Setting password has been entered via the any external communications inter-
face three times within a three-minute time span, the REMOTE ACCESS DENIED FlexLogic™ operand will be set to “On” and
the G60 will not allow Settings or Command access via the any external communications interface for the next ten minutes.
The
REMOTE ACCESS DENIED FlexLogic™ operand will be set to “Off” after the expiration of the ten-minute timeout.