GE Multilin G60 Generator Protection System 2-25
2 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS
2
2.2.14 APPROVALS
APPROVALS
2.2.15 MAINTENANCE
MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds) of torque.
CLEANING
Normally, cleaning is not required; but for situations where dust has accumulated on the faceplate display, a dry cloth can be used.
Units that are stored in a de-energized state should be powered up once per year, for one hour continuously, to avoid deterioration
of electrolytic capacitors.
COMPLIANCE APPLICABLE
COUNCIL DIRECTIVE
ACCORDING TO
CE compliance Low voltage directive EN60255-5
EMC directive EN60255-26 / EN50263
EN61000-6-5
North America --- UL508
--- UL1053
--- C22.2 No. 14