GE Multilin G60 Generator Protection System A-1
APPENDIX A A.1 PARAMETER LISTS
A
Appendices
APPENDIX A FlexAnalog and FlexInteger Parameters
A.1Parameter Lists A.1.1 FLEXANALOG ITEMS
Table A–1: FLEXANALOG DATA ITEMS (Sheet 1 of 23)
ADDRESS FLEXANALOG NAME UNITS DESCRIPTION
5728 Stator Diff Iad Amps Stator differential phase A current (Iad)
5730 Stator Rest Iar Amps Stator restraint phase A current (Iar)
5732 Stator Diff Ibd Amps Stator differential phase B current (Ibd)
5734 Stator Rest Ibr Amps Stator restraint phase B current (Ibr)
5736 Stator Diff Icd Amps Stator differential phase C current (Icd)
5738 Stator Rest Icr Amps Stator restraint phase C current (Icr)
5744 Stator Gnd Vn 3rd Volts Stator ground Vn third harmonic voltage
5746 Stator Gnd Vn+V0 3rd Volts Stator ground Vn+V0 third harmonic voltage
5748 Stator Gnd V0 3rd Volts Stator ground V0 third harmonic voltage
5760 Sns Dir Power 1 Watts Sensitive directional power 1 actual value
5762 Sns Dir Power 2 Watts Sensitive directional power 2 actual value
5792 RGF 1 Igd Mag Amps Restricted ground fault 1 differential ground current magnitude
5794 RGF 1 Igr Mag Amps Restricted ground fault 1 restricted ground current magnitude
5796 RGF 2 Igd Mag Amps Restricted ground fault 2 differential ground current magnitude
5798 RGF 2 Igr Mag Amps Restricted ground fault 2 restricted ground current magnitude
5800 RGF 3 Igd Mag Amps Restricted ground fault 3 differential ground current magnitude
5802 RGF 3 Igr Mag Amps Restricted ground fault 3 restricted ground current magnitude
5804 RGF 4 Igd Mag Amps Restricted ground fault 4 differential ground current magnitude
5806 RGF 4 Igr Mag Amps Restricted ground fault 4 restricted ground current magnitude
5808 RGF 5 Igd Mag Amps Restricted ground fault 5 differential ground current magnitude
5810 RGF 5 Igr Mag Amps Restricted ground fault 5 restricted ground current magnitude
5812 RGF 6 Igd Mag Amps Restricted ground fault 6 differential ground current magnitude
5814 RGF 6 Igr Mag Amps Restricted ground fault 6 restricted ground current magnitude
5856 Freq Rate 1 Value Hz/s Frequency rate of change 1 actual value
5860 Freq Rate 2 Value Hz/s Frequency rate of change 2 actual value
5864 Freq Rate 3 Value Hz/s Frequency rate of change 3 actual value
5868 Freq Rate 4 Value Hz/s Frequency rate of change 4 actual value
6144 SRC 1 Ia RMS Amps Source 1 phase A current RMS
6146 SRC 1 Ib RMS Amps Source 1 phase B current RMS
6148 SRC 1 Ic RMS Amps Source 1 phase C current RMS
6150 SRC 1 In RMS Amps Source 1 neutral current RMS
6152 SRC 1 Ia Mag Amps Source 1 phase A current magnitude
6154 SRC 1 Ia Angle Degrees Source 1 phase A current angle
6155 SRC 1 Ib Mag Amps Source 1 phase B current magnitude
6157 SRC 1 Ib Angle Degrees Source 1 phase B current angle
6158 SRC 1 Ic Mag Amps Source 1 phase C current magnitude
6160 SRC 1 Ic Angle Degrees Source 1 phase C current angle
6161 SRC 1 In Mag Amps Source 1 neutral current magnitude
6163 SRC 1 In Angle Degrees Source 1 neutral current angle
6164 SRC 1 Ig RMS Amps Source 1 ground current RMS
6166 SRC 1 Ig Mag Degrees Source 1 ground current magnitude
6168 SRC 1 Ig Angle Amps Source 1 ground current angle
6169 SRC 1 I_0 Mag Degrees Source 1 zero-sequence current magnitude
6171 SRC 1 I_0 Angle Amps Source 1 zero-sequence current angle
6172 SRC 1 I_1 Mag Degrees Source 1 positive-sequence current magnitude