10-16 G60 Generator Protection System GE Multilin
10.2 PHASE DISTANCE THROUGH POWER TRANSFORMERS 10 APPLICATION OF SETTINGS
10
The Zone 3 settings are:
(EQ 10.40)
PHS DIST Z3 REACH: "2.60"
PHS DIST Z3 RCA: "89"
PHS DIST Z3 XMFR VOL CONNECTION: "Yd11"
PHS DIST Z3 XMFR CUR CONNECTION: "None"
Z
3
0.127 90 0.006 88+
315
13.8
-----------
1600
2625
-------------
2.601 89.4==