%SB0001-9 reserved
%SB0010
BAD_RAM
Set when the CPU detects corrupted RAM memory at powerup.
Cleared when RAM memory is valid at powerup.
%SB0011
BAD_PWD
Set when a password access violation occurs. Cleared when the PLC
fault table is cleared.
%SB0012 reserved
%SB0013
SFT_CPU
Set when the CPU detects an unrecoverable error in the software.
Cleared by clearing the PLC fault table.
%SB0014
STOR_ER
Set when an error occurs during a programmer store operation.
Cleared when a store operation is completed successfully.
%SC0001-8 reserved
%SC0009
ANY_FLT
Set when any fault occurs. Cleared when both fault tables have no
entries.
%SC0010
SY_FLT
Set when any fault occurs that causes an entry to be placed in the PLC
fault table. Cleared when the PLC fault table has no entries.
%SC0011
IO_FLT
Set when any fault occurs that causes an entry to be placed in the I/O
fault table. Cleared when the I/O fault table has no entries.
%SC0012
SY_PRES
Set as long as there is at least one entry in the PLC fault table. Cleared
when the PLC fault table has no entries.
%SC0013
IO_PRES
Set as long as there is at least one entry in the I/O fault table. Cleared
when the I/O fault table has no entries.
%SC0014
HRD_FLT
Set when a hardware fault occurs. Cleared when both fault tables have
no entries.
%SC0015
SFT_FLT
Set when a software fault occurs. Cleared when both fault tables have
no entries.