Modules Located in Single-ended Expansion Rack
The table below shows timing for modules located in a single-ended expansion rack with
a non-isolated Expansion Receiver module ((C200ERM002). This type of system does
NOT have an Expansion Transmitter module (IC200ETM001) in the main rack.
Module Type
CPU005/CPUE05 CPU001/CPU002
Local Single Rack Local Single Rack
Input Output Input Output
Discrete Input Type 1
127
191
Discrete Input Type 2
179
262
Discrete Output Type 1
116
167
Discrete Output Type 2
167
222
Discrete Output w/ ESCP
176
260
Per Point Fault Reporting
Intelligent Discrete Input 20 Points
643
763
Intelligent Discrete Output 12 Points
714
756
Analog Input 4 Channels
317
389
Analog Input 8 Channels
527
631
Analog Input 15 Channels
896
1054
Analog Output 2 Channels
204
266
Analog Output 4 Channels
296
374
Analog Output 8 Channels
480
592
Analog Output 12 Channels
664
809
Intelligent Analog Input 4 Channels
438
533
Intelligent Analog Input 7 Channels
479
580
Intelligent Analog Input 8 Channels
493
596
Intelligent Analog Output 4 Channels
484
613
PLC Network Comm Profibus-DP Slave
†† †† †† ††
DeviceNet Network Master/Slave
†† †† †† ††
Mixed modules have both and input and output scan time values.
††
Network Communications Modules (NCM) Scan Impact Times vary depending upon the network
configuration.
Appendix A Performance Data GFK-1503E User Manual 311