EasyManua.ls Logo

GE VersaMax PLC

GE VersaMax PLC
318 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.9 Timer and Counter Functions
This section describes the timing and counting functions of the Instruction Set. The data
associated with these functions is retentive through power cycles.
On-delay Stopwatch Timer
Off-delay Timer
On-delay Timer
Up Counter
Down Counter
Time-tick Contacts
In addition to the Timer functions of the Instruction Set, the VersaMax PLC has four
time-tick contacts. These contacts can be used to provide regular pulses of power flow to
other program functions. The four time-tick contacts have time durations of 0.01 second,
0.1 second, 1.0 second, and 1 minute.
The state of these contacts does not change during the execution of the sweep. These
contacts provide a pulse having an equal on and off time duration.
The contacts are referenced as T_10MS (0.01 second), T_100MS (0.1 second), T_SEC
(1.0 second), and T_MIN (1 minute).
The following timing diagram represents the on/off time duration of these contacts.
X
X/2
SEC
T XXXXX
X/2
SEC
SEC
These time-tick contacts represent specific locations in %S memory.
Function Block Data Required for Timers and Counters
Each timer or counter uses three words (registers) of %R memory to store the following
information:
current value (CV)
word 1
preset value (PV)
word 2
control word word 3
When you enter a timer or counter, you must enter a beginning address for these three
words (registers). Do not use consecutive registers for the 3 word timer/counter blocks.
Timers and counters will not work if you place the current value of a block on top of the
preset for the previous block.








184 GFK-1503E VersaMax PLC User Manual
For public disclosure

Table of Contents

Related product manuals