EasyManua.ls Logo

GE VersaMax PLC

GE VersaMax PLC
318 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.10 SVCREQ 9: Read Sweep Time from Beginning of
Sweep
Use SVCREQ 9 to read the time in milliseconds since the start of the sweep. The data
format is unsigned 16-bit integer.
11.10.1 Output Parameter Block Format for
SVCREQ 9
The parameter block is an output parameter block only; it has a length of one word
address time since start of sweep
11.10.1.1 Example of SVCREQ 9
In the following example, the elapsed time from the start of the sweep is always read into
location %R0200. If it is greater than 100ms, internal coil %M0200 is turned on.
CONST
00009
SVC_
REQ
FNC
PARM
I1
I2
Q
GT_
INT
CONST
0100
%M0200
%R0200
%R0200
The Service Request Function GFK-1503E User Manual 211
For public disclosure

Table of Contents

Related product manuals