crsp_tout
Transfer/Response timeout value (in
seconds)
16 (0010H) 10 3600 (0e10H)
fflush
ARP cache timeout interval (in seconds) 0 604800 (93a80H) 600 (0258H)
gctl_port
UDP port for Ethernet Global Data control
messages
7937 (1f01H) 0-65535 (ffffH)
gdata_port
UDP port for point-to-point Ethernet Global
Data messages
18246 (4746H) 0-65535 (ffffH)
gbcast_ttl
IP time-to-live for global broadcast messages
(hop count)
1 (1H) 0-255 (00ffH)
gucast_ttl
IP time-to-live for point-to-point messages
(hop count)
16 (10H) 0-255 (00ffH)
gXX_udp UDP port for host group XX 18246 (4746H) 0-65535 (ffffH)
gXX_ttl
IP time-to-live for host group (multicast)
messages (hop count)
1 (1H) 0-255 (00ffH)
gXX_addr
IP group address for host group XX (must be
class D address)
224.0.7.XX
224.0.0.2 -
239.255.255.255
ittl
IP header default time-to-live (hop count) 64 (0040H) 0-255 (00ffH)
ifrag_tmr IP fragment timeout interval (in seconds) 3 (0003H) 0-65535 (ffffH)
wnodelay TCP nodelay option (0=inactive, 1=active) 0 (000H)
0,1
wkal_idle TCP keepalive timer value (in seconds)
240 (00f0H) = 4.0
minutes
0-65535 (ffffH)
wkal_cnt TCP keepalive probe count 2 (0002H)
wkal_intvl TCP keepalive probe interval (in seconds) 60 (003cH)
wmsl
TCP maximum segment lifetime (in seconds) 30 (001eH)
wsnd_buf TCP send buffer size in bytes 4096 (1000H)
0-32767 (7fffH)
wrcv_buf TCP receive buffer size in bytes 4096 (1000H)
nmin_poll1
NTP min. poll interval for host 1. The value
specifies log(2) of the interval in seconds (eg:
the value 3 means 8 secs, 4 means 16 sec,
etc)
6 (0006H) = 64 seconds 4 14 (000eH)
nmax_poll1
NTP maximum poll interval for host 1 (in log
(2) of seconds)
10 (000aH) = 1024 sec. (16 16384 sec)
nmin_poll2
NTP min. poll interval for host 2 (in log(2) of
seconds)
6 (0006H) = 64 sec.
nmax_poll2
NTP max. poll interval for host 2 (in log(2) of
seconds)
10 (000aH) = 1024 sec.
nmin_poll3
NTP min. poll interval for host 3 (in log(2) of
seconds)
6 (0006H) = 64 sec.
nmax_poll3
NTP max. poll interval for host 3 (in log(2) of
seconds)
10 (000aH) = 1024 sec.