Basic Programming 5-11
September 2007
SET HIGH INPUT VALUE
Option
The Set High Input Value option lets you specify the %O
2
value in the
gas that corresponds to a 20.00 mA current at the analog output.
Note: This option appears if DriftCal is ON or OFF and if a one- or
two-gas calibration has been selected.
To use the Set High Input Value option, proceed as follows:
1. Press
[N] until the following prompt appears:
2. At the above screen, do one of the following:
Press [Y] or [ENTER] to accept the current high input value
(100.00 in the above example). Then, go to Step 4.
Use the numeric keys to enter a new high input value (25.00 in
the example that follows). Then, go to Step 3.
3. If you entered a new high input value:
4. Complete the procedure as follows:
You may now do one of the following:
Press [N] as many times as necessary to select another Basic Menu
option. Then, press
[Y] and proceed to the appropriate section for
instructions.
Press [N] repeatedly until the Resume? option appears. Then, press
[Y] to return to Operate Mode.
BASIC MENU
Press [Y] or [ENTER] to set the
high (20 mA) input value.
Set High Input Value?
mA Output 20 mA Value
Go to Step 2.
%O2 [100.00]:
mA Output 20 mA Value
Press [Y] or [ENTER] to accept the
new high (20 mA) input value.
%O2 [100.00]:25.00
BASIC MENU
The High Input Value has been
set.
Set High Input Value?