EasyManuals Logo

GEA VARIVENT X R Series User Manual

GEA VARIVENT X R Series
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
5 Assembly and installation
This chapter
contains information and instructions about the assembly and installation
of the valve.
It is addressed to all persons who carry out actions related to the valve.
INFO During assembly and installation, observe chapter
2 Safety
of this Operat-
ing Instructions.
5.1 Notes on installation
The valve can be installed in any position. Steps must be taken to ensure that the valve
housing and the pipe system can drain properly.
If the valve is installed in the horizontal position, pay attention that the vent hole in the
actuator is aligned horizontally on one side.
To avoid damage, ensure that the valve is installed into the pipe system without tension
and no objects remain in the system after assembly (e.g. tools, screws, lubrication oils).
If the valve is installed horizontally, the stress on the valve stem seals is higher than in
the vertical installation position. Therefore, support the actuator and regularly check
the valve for leakage.
5.2 Control top
If the external valves are connected in a control top with several solenoid valves, make
sure that the control air pressure in the main actuator does not fall below the operating
pressure.
5.3 Install the valve with detachable pipe connection
elements
Prerequisites
The pipe is drained, and cleaned or rinsed, if necessary
.
The
pipe section for the valve to be mounted must be separated from the re-
maining pipe system.
1. Fit valves with detachable pipe connection elements using suitable connection
ttings – directly into the pipe system.
Þ
Valve is installed.
5.4 Install valve with welding ends
WARNING
Spring tension in the valve (NC)
Danger of injury when opening the clamp connections on the actuator or on the
housing as the r
eleased spring pr
etension will suddenly lift the actuator.
Therefore, release the spring tension before detaching the clamp connection by
pressurising the actuator with compressed air at max. 8 bar.
5.1 Notes on installation - 35 / 104

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GEA VARIVENT X R Series and is the answer not in the manual?

GEA VARIVENT X R Series Specifications

General IconGeneral
BrandGEA
ModelVARIVENT X R Series
CategoryControl Unit
LanguageEnglish

Related product manuals