87
4. CONFIGURATION
4.13.8. H.PB - Proportional heating band or hysteresis in ON-OFF control
Acronym Scrolling message Submenu Attributes
H.PB HEATING PROPORTIONAL BAND OR ON/OFF HYST PID R W
The parameter shows and sets the proportional heating band or hysteresis in the ON-OFF control, calculated as a per-
centage of full scale of the main input.
Unit of measurement: %
Options: 0.0...999.9
4.13.9. H.IT - Integral heating time
Acronym Scrolling message Submenu Attributes
H.IT HEATING INTEGRAL TIME PID R W
The parameter shows and sets the integral heating time.
Unit of measurement: Minutes
Options: 0.00...99.99
4.13.10. H.DT - Derivative heating time
Acronym Scrolling message Submenu Attributes
H.DT HEATING DERIVATIVE TIME PID R W
The parameter shows and sets the derivative heating time.
Unit of measurement: Minutes
Options: 0.00...99.99
4.13.11. H.P.HI - Maximum limit of heating power
Acronym Scrolling message Submenu Attributes
H.P.HI HEATING POWER HIGH LIMIT PID R W
The parameter shows and sets the maximum limit of heating power.
Unit of measurement: %
Options: 0.0...100.0
4.13.12. H.P.LO - Minimum limit of heating power
Acronym Scrolling message Submenu Attributes
H.P.LO HEATING POWER LOW LIMIT PID R W
The parameter shows and sets the minimum limit of heating power.
Not available for dual action. The power of PID heating/cooling control (called dual action) is limited by the values of
H.P.HI and C.P.HI.
Unit of measurement: %
Options: 0.0...100.0